Siemens SINAMICS G120D CU240D-2 DP Manual page 463

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

r9712
CO: SI Motion diagnostics pos. act. val. motor side (processor 1) / SI Mtn s_act motP1
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: -
CU250D-2_PN_F
Unit group: -
CU250D-2_DP_F
Min
-
Description:
Displays the actual motor-side position actual value for the motion monitoring functions on processor 1.
Note:
The display is updated in the safety monitoring clock cycle.
r9713[0...5]
CO: SI Motion diagnostics position actual value load side / SI Mtn s_act load
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: -
CU250D-2_PN_F
Unit group: -
CU250D-2_DP_F
Min
-
Description:
Displays the actual load-side actual values of both monitoring channels and their difference.
Index:
[0] = Load-side actual value on processor 1 (P1)
[1] = Load-side actual value on processor 2 (P2)
[2] = Load-side actual value difference P1 - P2
[3] = Load-side maximum actual value difference P1 - P2
[4] = Load-side actual value as safe position via PROFIsafe
[5] = Load-side additional actual value difference CU - second channel
Dependency:
Refer to: r9708, r9724
Note:
The value of this parameter is displayed in r9708 with units (mm or degrees).
The display is updated in the safety monitoring clock cycle.
For index 0:
The display of the load-side position actual value on processor 1 is updated in the monitoring clock cycle.
For index 1:
The display of the load-side position actual value on processor 2 is updated in the CDC clock cycle (r9724) and
delayed by one CDC clock cycle.
For index 2:
The difference between the load-side position actual value on processor 1 and load-side position actual value on
processor 2 is updated in the CDC clock cycle (r9724) and delayed by one CDC clock cycle.
For index 3:
The maximum difference between the load-side position actual value on processor 1 and the load-side position
actual value on processor 2.
For index 4:
The content corresponds to the value in index 0.
CDC: Crosswise Data Comparison
r9714[0...2]
CO: SI Motion diagnostics velocity (processor 1) / SI Mtn diag v P1
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: -
CU250D-2_PN_F
Unit group: -
CU250D-2_DP_F
Min
- [rpm]
Description:
Displays the actual velocity values for the motion monitoring functions on processor 1.
Index:
[0] = Load-side velocity actual value on processor 1
[1] = Actual SAM/SBR velocity limit on processor 1
[2] = Actual SLS velocity limit on the processor 1
Dependency:
Refer to: r9732
Notice:
For index 2:
This SLS velocity limit can, as a result of conversion into the internal monitoring format, deviate from the specified
SLS velocity limit (see r9732).
Note:
The display is updated in the safety monitoring clock cycle.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [rpm]
2 Parameters
2.2 List of parameters
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Integer32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [rpm]
463