p2172[0...n]
DC link voltage threshold value / Vdc thresh val
Access level: 3
Can be changed: U, T
Unit group: 5_2
Min
0 [V]
Description:
Sets the DC link voltage threshold value for the following messages:
"Vdc_act <= Vdc_threshold p2172" (BO: r2197.9)
"Vdc_act > Vdc_threshold p2172" (BO: r2197.10)
Dependency:
Refer to: p2173
p2173[0...n]
DC link voltage comparison delay time / t_del Vdc
Access level: 3
Can be changed: U, T
Unit group: -
Min
0 [ms]
Description:
Sets the delay time for the comparison of the DC link voltage r0070 with the threshold value p2172.
Dependency:
Refer to: p2172
p2174[0...n]
Torque threshold value 1 / M_thresh val 1
Access level: 3
Can be changed: U, T
Unit group: 7_1
Min
0.00 [Nm]
Description:
Sets the torque threshold value for the messages:
"Torque setpoint < torque threshold value 1 and n_set reached" (BO: r2198.9)
"Torque setpoint < torque threshold value 1" (BO: r2198.10)
"Torque setpoint > torque threshold value 1" (BO: r2198.13)
Dependency:
Refer to: p2195, r2198
p2175[0...n]
Motor blocked speed threshold / Mot lock n_thresh
Access level: 3
Can be changed: U, T
Unit group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold for the message "Motor blocked" (BO: r2198.6).
Dependency:
Refer to: p0500, p2177, r2198
Refer to: F07900
Note:
The following applies for encoderless vector control for induction motors:
At low speeds in open-loop speed controlled operation (see p1755, p1756), a blocked motor cannot be detected.
The following applies for encoderless vector control for permanent magnet synchronous motors:
At low speeds in open-loop speed controlled operation (see p1755, p1756), a blocked motor can only be detected if
p2175 = p1755, and p1750.6 is set to 1.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
2000 [V]
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: -
Unit selection: p0505
Max
20000000.00 [Nm]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
800 [V]
Data type: Unsigned16
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
10 [ms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8012
Factory setting
5.13 [Nm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8012
Factory setting
120.00 [rpm]
305