2 Parameters
2.2 List of parameters
p2042
PROFIBUS Ident Number / PB Ident No.
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
Unit group: -
Min
0
Description:
Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value:
0:
1:
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
Every change only becomes effective after a POWER ON.
r2043.0...2
BO: PROFIdrive PZD state / PD PZD state
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the PROFIdrive PZD state.
Bit field:
Bit
00
02
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
p2044
PROFIdrive fault delay / PD fault delay
Access level: 3
Can be changed: U, T
Unit group: -
Min
0 [s]
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency:
Refer to: r2043
Refer to: F01910
p2047
PROFIBUS additional monitoring time / PB suppl t_monit
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: U, T
CU250D-2_DP_F
Unit group: -
Min
0 [ms]
Description:
Sets the additional monitoring time to monitor the process data received via PROFIBUS.
Enables short bus faults to be compensated.
If no process data is received within this time, then an appropriate message is output.
Dependency:
Refer to: F01910
Note:
For controller STOP, the additional monitoring time is not effective.
272
SINAMICS
VIK-NAMUR
Signal name
Setpoint failure
Fieldbus oper
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
100 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
20000 [ms]
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned8
Dyn. index: -
Func. diagram: 2410
Factory setting
-
0 signal
No
No
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2410
Factory setting
0 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2410
Factory setting
0 [ms]
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313