Siemens SINAMICS G120D CU240D-2 DP Manual page 400

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Note:
For bit 00:
All of the help functions for long stator motors can be enabled/disabled using this bit.
For bit 01:
When the bit is set, bit 14 (parking encoder active) is set to 0 in the encoder status word GX_ZSW independent of
whether the encoder is parked or not.
p3900
Completion of quick commissioning / Compl quick_comm
Access level: 1
Can be changed: C(1)
Unit group: -
Min
0
Description:
Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets that
depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p15 and p1500 are
re-established and all of the dependent motor, open-loop and control-loop control parameters are calculated
(corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p15 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value:
0:
1:
2:
3:
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters
associated with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (p0300), then the following parameters are reset with p3900 > 0 in order to
restore the situation that applied when commissioning the drive for the first time:
induction motor: p0320, p0352, p0362 ... p0369, p0604, p0605, p0626 ... p0628
synchronous motor: p0326, p0327, p0352, p0604, p0605
r3925[0...n]
Identification final display / Ident final_disp
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the commissioning steps that have been carried out.
Bit field:
Bit
00
02
03
08
11
400
No quick parameterization
Quick parameterization after parameter reset
Quick parameterization (only) for BICO and motor parameters
Quick parameterization for motor parameters (only)
Signal name
Motor/control parameters calculated (p0340
= 1, p3900 > 0)
Motor data identification carried out at
standstill (p1910 = 1)
Rotating measurement carried out (p1960 =
1, 2)
Motor identification data have been
automatically backed up
Automatic parameterization as standard
drive control
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
-
0 signal
No
No
No
No
No
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
FP
-
-
-
-
-