[0] = Catalog
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
p0210
Drive unit line supply voltage / U_connect
Access level: 3
Can be changed: C(2), T
Unit group: -
Min
1 [V]
Description:
Sets the drive unit supply voltage (rms value of the phase-to-phase line supply voltage).
Dependency:
Set p1254, p1294 (automatic detection of the Vdc switch-on levels) = 0.
The switch-in thresholds of the Vdc_max controller (r1242, r1282) are then directly determined using p0210.
Notice:
If, in the switched-off state (pulse inhibit), the supply voltage is higher than the entered value, the Vdc controller may
be automatically de-activated in some cases to prevent the motor from accelerating the next time the system is
switched on. In this case, an appropriate alarm A07401 is output.
Note:
Setting ranges for p0210 as a function of the rated power unit voltage:
U_rated = 230 V:
- p0210 = 200 ... 240 V
U_rated = 400 V:
- p0210 = 380 ... 480 V
U_rated = 690 V:
- p0210 = 660 ... 690 V
p0230
Drive filter type motor side / Drv filt type mot
Access level: 1
Can be changed: C(1, 2)
Unit group: -
Min
0
Description:
Sets the type of the filter at the motor side.
Value:
0:
1:
2:
4:
Dependency:
The following parameters are influenced using p0230:
p0230 = 1:
--> p0233 (power unit, motor reactor) = filter inductance
p0230 = 4:
--> p0290 (power unit overload response) = inhibit pulse frequency reduction
--> p1802 (modulator modes) = space vector modulation without overcontrol
The user must set the following parameters according to the data sheet of the sine-wave filter and also the user must
check whether they are permitted.
--> p0233 (power unit, motor reactor) = filter inductance
--> p0234 (power unit sine-wave filter capacitance) = filter capacitance
--> p1082 (maximum speed) = Fmax filter / pole pair number
--> p1800 (pulse frequency) >= nominal pulse frequency of the filter
Refer to: p0233, p0234, p0290, p1082, p1800, p1802
Note:
If a filter type cannot be selected, then this filter type is not permitted for the power unit.
For sine-wave filters, the test pulse evaluation to detect short-circuits is always de-activated.
p0230 = 1:
Power units with output reactor are limited to output frequencies of 150 Hz.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
No filter
Motor reactor
dv/dt filter
Sine-wave filter third-party
Calculated: -
Scaling: -
Unit selection: -
Max
63000 [V]
Calculated: -
Scaling: -
Unit selection: -
Max
4
2 Parameters
2.2 List of parameters
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
400 [V]
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0