STO: Safe Torque Off
F30625
SI P2: Sign-of-life error in safety data
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on processor 2 has detected an error in the sign-of-life of the safety
data and initiated a STOP A.
- there is a communication error between processor 1 and processor 2 or communication has failed.
- a time slice overflow of the safety software has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- select Safe Torque Off and de-select again.
- carry out a POWER ON (switch-off/switch-on).
- check whether additional faults are present and if required, perform diagnostics.
- check the electrical cabinet design and cable routing for EMC compliance
F30649
SI P2: Internal software error
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal error in the Safety Integrated software on processor 2 has occurred.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- re-commission the "Safety Integrated" function and carry out a POWER ON.
- contact Technical Support.
- replace Control Unit.
F30650
SI P2: Acceptance test required
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on processor 2 requires an acceptance test.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, interpret decimal):
130: Safety parameters for processor 2 not available.
Note:
This fault value is always output when Safety Integrated is commissioned for the first time.
1000: Reference and actual checksum on processor 2 are not identical (booting).
- at least one checksum-checked piece of data is defective.
- safety parameters set offline and loaded into the Control Unit.
2000: Reference and actual checksum on processor 2 are not identical (commissioning mode).
- reference checksum incorrectly entered on processor 2 (p9899 not equal to r9898).
2003: Acceptance test is required as a safety parameter has been changed.
2010: Enable of safety-related brake control between the two monitoring channels differ (p9602 not equal to p9802).
9999: Subsequent response of another safety-related fault that occurred when booting that requires an acceptance
test.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
4 Faults and alarms
4.2 List of faults and alarms
923