A07531
Drive: Command Data Set CDS not present
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected command data set is not available (p0836 > p0170). The command data set was not changed over.
See also: p0810 (Command data set selection CDS bit 0), p0811 (Command data set selection CDS bit 1), r0836
(Command Data Set CDS selected)
Remedy:
- select the existing command data set.
- set up additional command data sets.
A07550 (F, N)
Drive: Not possible to reset encoder parameters
Message class:
Hardware/software error (1)
Reaction:
NONE
Acknowledge:
NONE
Cause:
When carrying out a factory setting (e.g. using p0970 = 1), it was not possible to reset the encoder parameters.
Alarm value (r2124, interpret decimal):
Component number of the encoder involved.
Remedy:
Repeat the operation.
F07552 (A)
Drive encoder: Encoder configuration not supported
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The requested encoder configuration is not supported. Only bits may be requested in p0404 that are signaled as
being supported by the encoder evaluation in r0456.
Fault value (r0949, interpret decimal):
ccccbbaa hex: cccc = fault cause, bb = component number, aa = encoder data set
cccc = 1: encoder sin/cos with absolute track (is supported by SME25).
cccc = 3: Squarewave encoder (this is supported by SMC30).
cccc = 4: sin/cos encoder (this is supported by SMC20, SMI20, SME20, SME25).
cccc = 10: DRIVE-CLiQ encoder (is supported by DQI).
cccc = 12: sin/cos encoder with reference mark (this is supported by SME20).
cccc = 15: Commutation with zero mark for separately-excited synchronous motors with VECTORMV.
cccc = 23: Resolver (this is supported by SMC10, SMI10).
cccc = 65535: Other function (compare r0456 and p0404).
See also: p0404 (Encoder configuration effective), r0456 (Encoder configuration supported)
Remedy:
- check the encoder parameterization (p0400, p0404).
- use the matching encoder evaluation (r0456).
F07553 (A)
Drive encoder: Sensor Module configuration not supported
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The Sensor Module does not support the requested configuration.
For incorrect p0430 (cc = 0), the following applies:
- in p0430 (requested functions), at least 1 bit was set that is not set in r0458 (supported functions) (exception: Bit 19,
28, 29, 30, 31).
- p1982 > 0 (pole position identification requested), but r0458.16 = 0 (pole position identification not supported).
For incorrect p0437 (cc = 1), the following applies:
- in p0437 (requested functions), at least 1 bit was set that is not set in r0459 (supported functions).
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
4 Faults and alarms
4.2 List of faults and alarms
881

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents