Dependency:
Refer to: p9651
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
Rounding effects can occur in the last decimal place of the parameterized time.
The debounce time is rounded to whole milliseconds. It specifies the maximum duration of a fault pulse at the fail-
safe digital inputs with no reaction/influence on the selection or deselection of the Safety Basic Functions.
Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
r9871
SI common functions (processor 2) / SI common fct P2
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: -
CU250D-2_PN_F
Unit group: -
CU250D-2_DP_F
Min
-
Description:
Displays the supported Safety Integrated monitoring functions.
Processor 2 determines this display.
Bit field:
Bit
00
02
04
05
06
07
11
12
Dependency:
Refer to: r9771
Note:
STO: Safe Torque Off
r9871
SI common functions (processor 2) / SI common fct P2
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: -
Unit group: -
Min
-
Description:
Displays the supported Safety Integrated monitoring functions.
Processor 2 determines this display.
Bit field:
Bit
00
06
Dependency:
Refer to: r9771
Note:
STO: Safe Torque Off
r9872.0...21
CO/BO: SI status (processor 2) / SI Status P2
CU240D-2_DP_F
Access level: 2
CU240D-2_PN_F
Can be changed: -
CU250D-2_PN_F
Unit group: -
CU250D-2_DP_F
Min
-
Description:
Displays the Safety Integrated status on processor 2.
Bit field:
Bit
00
01
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Signal name
STO supported via terminals
Extended Functions supported (p9501 > 0)
Extended Functions PROFIsafe supported
Extended Functions integrated in drive
supported (p9601.2 = 1)
Basic Functions PROFIsafe supported
Extended Functions encoderless supported Yes
Extended Functions SDI supported
Extended Functions SSM encoderless
supported
Signal name
STO supported via terminals
Basic Functions PROFIsafe supported
Signal name
STO selected on processor 2
STO active on processor 2
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
2 Parameters
2.2 List of parameters
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2804
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2804
Factory setting
-
0 signal
No
No
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2804
Factory setting
-
0 signal
No
No
FP
2804
2804
-
-
-
-
-
-
FP
2804
-
FP
2810
2810