Dependency:
"Quick commissioning" must be carried out (p0010 = 1, p3900 > 0) before executing the motor data identification
routine!
When selecting the motor data identification routine, the drive data set changeover is suppressed.
Refer to: p1900
Refer to: F07990, A07991
Notice:
After the motor data identification (p1910 > 0) has been selected, alarm A07991 is output and a motor data
identification routine is carried out as follows at the next switch-on command:
- current flows through the motor and a voltage is present at the drive converter output terminals.
- during the identification routine, the motor shaft can rotate through a maximum of half a revolution.
- however, no torque torque is generated.
Note:
If there is a motor holding brake, it must be open (p1215 = 2).
To permanently accept the determined settings they must be saved in a non-volatile fashion (p0971).
When setting p1910, the following should be observed:
1. "With acceptance" means:
The parameters specified in the description are overwritten with the identified values and therefore have an influence
on the controller setting.
2. "Without acceptance" means:
The identified parameters are only displayed in the range r1912 ... r1926 (service parameters). The controller
settings remain unchanged.
3. For settings 27 and 28, the AVC configuration set using p1840 is active.
The switch-on command must remain set during a measurement and after the measurement has been completed,
the drive automatically resets it. The duration of the measurements can lie between 0.3 s and several minutes. This
time is mainly influenced by the motor size. At the end of the motor data identification, p1910 is automatically set to 0,
if only the stationary measurement is selected, then p1900 is also reset to 0, otherwise, the rotating measurement is
activated.
p1910
Motor data identification selection / MotID selection
CU250D-2_PN_F
Access level: 3
CU250D-2_DP_F
Can be changed: T
Unit group: -
Min
0
Description:
Sets the motor data identification routine.
The motor data identification routine is carried out after the next switch-on command.
p1910 = 1:
All motor data and the drive converter characteristics are identified and then transferred to the following parameters:
p0350, p0354, p0356, p0357, p0358, p0360, p1825, p1828, p1829, p1830
After this, the control parameter p0340 = 3 is automatically calculated.
p1910 = 20:
Only for internal SIEMENS use.
Value:
0:
1:
2:
20:
21:
22:
23:
24:
25:
26:
27:
28:
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Rectangular voltage vector input with filter
Triangular voltage vector input with filter
Enter voltage vector with DTC correction
Enter voltage vector with AVC
Enter voltage vector with DTC + AVC correction
Inhibited
Complete identification (ID) and acceptance of motor data
Complete identification (ID) of motor data without acceptance
Voltage vector input
Voltage vector input without filter
Rectangular voltage vector input without filter
Triangular voltage vector input without filter
Rectangular voltage vector input with filter
Triangular voltage vector input with filter
Enter voltage vector with DTC correction
Enter voltage vector with AVC
Enter voltage vector with DTC + AVC correction
Calculated: -
Scaling: -
Unit selection: -
Max
28
2 Parameters
2.2 List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
1
257

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents