p1563[0...n]
CO: Mom. of inertia estimator load torque direction of rotation pos. / J_est M pos
Access level: 3
Can be changed: U, T
Unit group: -
Min
-340.28235E36 [Nm]
Description:
Display and connector output for the monitored load torque in the positive direction of rotation.
The moment of inertia estimator estimates the load torque drawn while the speed is constant.
Dependency:
Refer to: p1400, p1560, p1561
p1564[0...n]
CO: Mom. of inertia estimator load torque direction of rotation neg. / J_est M neg
Access level: 3
Can be changed: U, T
Unit group: -
Min
-340.28235E36 [Nm]
Description:
Display and connector output for the monitored load torque in the negative direction of rotation.
The moment of inertia estimator estimates the load torque drawn while the speed is constant.
Dependency:
Refer to: p1400, p1560, p1561
p1570[0...n]
CO: Flux setpoint / Flex setp
Access level: 3
Can be changed: U, T
Unit group: -
Min
50.0 [%]
Description:
Sets the flux setpoint referred to rated motor flux.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
For p1570 > 100%, the flux setpoint increases as a function of the load from 100% (no-load operation) to the setting
in p1570 (above rated motor torque), if p1580 > 0% has been set.
p1573[0...n]
Flux threshold value magnetizing / Flux thresh magnet
Access level: 3
Can be changed: U, T
Unit group: -
Min
10.0 [%]
Description:
Sets the flux threshold value for enabling the speed setpoint and the end of magnetizing (r0056.4).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note:
The parameter only has an influence if the flux actual value reaches the threshold value p1573 more quickly during
magnetizing than the time set in p0346. This is generally the case when selecting fast magnetization (p1401 bit 6).
The parameter has no influence for flying restart (see p1200) and after DC braking (see p1231).
p1574[0...n]
Voltage reserve dynamic / U_reserve dyn
Access level: 3
Can be changed: U, T
Unit group: 5_1
Min
0.0 [Vrms]
Description:
Sets a dynamic voltage reserve.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Calculated: -
Scaling: p2003
Unit selection: -
Max
340.28235E36 [Nm]
Calculated: -
Scaling: p2003
Unit selection: -
Max
340.28235E36 [Nm]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.0 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.0 [%]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
150.0 [Vrms]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
0.00 [Nm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
0.00 [Nm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6722
Factory setting
100.0 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6722
Factory setting
100.0 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6723, 6724
Factory setting
10.0 [Vrms]
229