Siemens SINAMICS G120D CU240D-2 DP Manual page 64

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0322[0...n]
Maximum motor speed / Mot n_max
Access level: 1
Can be changed: C(1, 3)
Unit group: -
Min
0.0 [rpm]
Description:
Sets the maximum motor speed.
Dependency:
Refer to: p1082
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0322 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly.
Note:
The parameter has no significance for a value of p0322 = 0.
p0323[0...n]
Maximum motor current / Mot I_max
Access level: 1
Can be changed: C(1, 3)
Unit group: -
Min
0.00 [Arms]
Description:
Sets the maximum permissible motor current (e.g. de-magnetizing current for synchronous motors).
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0323 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly.
Note:
The parameter has no effect for induction motors.
The parameter has not effect for synchronous motors if a value of 0.0 is entered. The user-selectable current limit is
entered into p0640.
p0325[0...n]
Motor pole position identification current 1st phase / Mot PolID I 1st ph
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000 [Arms]
Description:
Sets the current for the 1st phase of the two-stage technique for pole position identification routine.
The current of the 2nd phase is set in p0329.
The two-stage technique is selected with p1980 = 4.
Dependency:
Refer to: p0329, p1980, r1984, r1985, r1987
Refer to: F07969
Notice:
When the motor code (p0301) is changed, it is possible that p0325 is not pre-assigned.
p0325 can be pre-assigned using p0340 = 3.
Note:
The value is automatically pre-assigned for the following events:
- For p0325 = 0 and automatic calculation of the closed-loop control parameters (p0340 = 1, 2, 3).
- for quick commissioning (p3900 = 1, 2, 3).
p0326[0...n]
Motor stall torque correction factor / Mot M_stall_corr
Access level: 4
Can be changed: C(3), U, T
Unit group: -
Min
5 [%]
Description:
Sets the correction factor for the stall torque/force at a 600 V DC link voltage.
64
Calculated: -
Scaling: -
Unit selection: -
Max
210000.0 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
20000.00 [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max
10000.000 [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max
300 [%]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.0 [rpm]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.00 [Arms]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.000 [Arms]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
100 [%]
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents