r0296
DC link voltage undervoltage threshold / Vdc U_lower_thresh
Access level: 3
Can be changed: -
Unit group: -
Min
- [V]
Description:
Threshold to detect a DC link undervoltage.
If the DC link voltage falls below this threshold, the drive unit is tripped due to a DC link undervoltage condition.
Dependency:
Refer to: F30003
r0297
DC link voltage overvoltage threshold / Vdc U_upper_thresh
Access level: 3
Can be changed: -
Unit group: -
Min
- [V]
Description:
Threshold to detect a DC link overvoltage.
If the DC link voltage exceeds the threshold specified here, the drive unit is tripped due to DC link overvoltage.
Dependency:
Refer to: F30002
p0300[0...n]
Motor type selection / Mot type sel
CU240D-2_DP
Access level: 2
CU240D-2_PN
Can be changed: C(1, 3)
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
0
Description:
Selecting the motor type.
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = induction motor
2 = synchronous motor
xx = motor without code number
xxx = motor with code number
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/IOP).
The following applies for values < 100:
Motor data must be manually entered.
The following applies for values >= 100:
Motor data are automatically loaded from an internal list.
Value:
0:
1:
2:
10:
13:
17:
19:
100:
101:
271:
277:
Dependency:
When selecting p0300 = 10 ... 19, parameters p0335, p0626, p0627, and p0628 of the thermal motor model are pre-
assigned as a function of p0307 and p0311.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
No motor
Induction motor
Synchronous motor
1LE1 induction motor (not a code number)
1LG6 induction motor (not a code number)
1LA7 induction motor (not a code number)
1LA9 induction motor (not a code number)
1LE1 induction motor
1PC1 induction motor
1FG1 synchronous geared motor without encoder
1FK7 synchronous motor without encoder
Calculated: -
Scaling: -
Unit selection: -
Max
- [V]
Calculated: -
Scaling: -
Unit selection: -
Max
- [V]
Calculated: -
Scaling: -
Unit selection: -
Max
277
2 Parameters
2.2 List of parameters
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
- [V]
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8750, 8760, 8850,
8864, 8950, 8964
Factory setting
- [V]
Data type: Integer16
Dyn. index: MDS
Func. diagram: 6310
Factory setting
0
57