Siemens SINAMICS G120D CU240D-2 DP Manual page 17

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

Can be changed
The "-" sign indicates that the parameter can be changed in any object state and that the
change will be effective immediately.
The information "C(x), T, U" ((x): optional) means that the parameter can be changed only in
the specified drive unit state and that the change will not take effect until the unit switches to
another state. This can be a single state or multiple states.
The following states are available:
• C(x) commissioning
• U
• T
Scaling
Specification of the reference variable with which a signal value is automatically converted for
a BICO interconnection.
The following reference variables are available:
• p2000 ... p2007: Reference speed, reference voltage, etc.
• PERCENT: 1.0 = 100 %
• 4000H: 4000 hex = 100 % (wort) or 4000 0000 hex = 100 % (double word)
• p0514: specific normalization
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Drive commissioning is in progress (p0010 > 0).
Pulses cannot be enabled.
The parameter can only be changed in the following drive commissioning settings
(p0010 > 0):
• C: Can be changed for all settings p0010 > 0.
• C(x): Can only be changed for the settings p0010 = x.
A modified parameter value does not take effect until drive commissioning mode is
exited with p0010 = 0.
Operation
Pulses are enabled.
Ready
The pulses are not enabled and the status "C(x)" is not active.
Refer to the description for p0514[0...9] and p0515[0...19] to p0524[0...19]
2.1 Overview of parameters
C: Commissioning
U: Run
T: Ready to run
2 Parameters
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents