Siemens SINAMICS G120D CU240D-2 DP Manual page 384

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Valid values are only displayed when the pulses are inhibited.
For index 0:
Display of the entered direct axis current id in Arms:
For index 1, 2, 3:
Display of the saturation curves of the direct axis flux psid(id, iq):
- r2969[1]: flux in Vsrms with respect to the direct axis current for iq = 0
- r2969[2]: flux in Vsrms with respect to the direct axis current for iq = 0.5* p2950
- r2969[3]: flux in Vsrms with respect to the direct axis current for iq = p2950
For index 4, 5, 6:
Displays the relative error of the current inversion (id(psid, iq) - id) / p2950:
- r2969[4]: error with respect to direct axis current for iq = 0
- r2969[5]: error with respect to direct axis current for iq = 0.5 * p2950
- r2969[6]: error with respect to direct axis current for iq = p2950
Index:
[0] = d-current
[1] = d-flux iq0
[2] = d-flux iq1
[3] = d-flux iq2
[4] = d-current error iq0
[5] = d-current error iq1
[6] = d-current error iq2
Note:
RESM: reluctance synchronous motor (synchronous reluctance motor)
p3110
External fault 3 switch-on delay / Ext fault 3 t_on
Access level: 3
Can be changed: U, T
Unit group: -
Min
0 [ms]
Description:
Sets the delay time for external fault 3.
Dependency:
Refer to: p2108, p3111, p3112
Refer to: F07862
p3111[0...n]
BI: External fault 3 enable / Ext fault 3 enab
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3112
Refer to: F07862
p3112[0...n]
BI: External fault 3 enable negated / Ext flt 3 enab neg
Access level: 3
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for the negated enable signal of external fault 3.
384
Calculated: -
Scaling: -
Unit selection: -
Max
1000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: 2546
Factory setting
0 [ms]
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: -
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: -
Factory setting
0
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents