2 Parameters
2.2 List of parameters
Notice:
When the DHCP mode is active (p8924 not equal to 0), then PROFINET communication via this interface is no longer
possible! However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note:
The interface configuration (p8920 and following) is activated with p8925.
The active DHCP mode is displayed in parameter r8934.
The parameter is not influenced by setting the factory setting.
p8925
PN interface configuration / PN IF config
CU240D-2_PN
Access level: 3
CU240D-2_PN_F
Can be changed: U, T
CU250D-2_PN_F
Unit group: -
Min
0
Description:
Setting to activate the interface configuration for the onboard PROFINET interface on the Control Unit.
p8925 is automatically set to 0 at the end of the operation.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p8920, p8921, p8922, p8923, p8924
Notice:
When the DHCP mode is active (p8924 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note:
For p8925 = 2:
The interface configuration (p8920 and following) is saved and activated after the next POWER ON.
For p8925 = 3:
The factory setting of the interface configuration is loaded after the next POWER ON.
p8929
PN remote controller number / PN rem ctrl num
CU240D-2_PN
Access level: 3
CU240D-2_PN_F
Can be changed: C
CU250D-2_PN_F
Unit group: -
Min
1
Description:
Sets the number of remote controllers expected for PROFINET onboard.
The "Shared Device" functionality is activated with a value = 2.
The drive is being accessed by two PROFINET controllers simultaneously:
- automation controller (SIMOTION or SIMATIC A-CPU).
- safety controller (SIMATIC F-CPU).
Value:
1:
2:
Notice:
The F CPU may only use PROFIsafe telegrams.
Note:
Changes only become effective after POWER ON.
r8930[0...239]
PN Name of Station actual / PN Name Stat act
CU240D-2_PN
Access level: 3
CU240D-2_PN_F
Can be changed: -
CU250D-2_PN_F
Unit group: -
Min
-
Description:
Displays the actual station name for the onboard PROFINET interface on the Control Unit.
430
No function
Reserved
Save and activate configuration
Delete configuration
Automation or Safety
Automation and Safety
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: -
Scaling: -
Unit selection: -
Max
2
Calculated: -
Scaling: -
Unit selection: -
Max
-
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
1
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
-
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313