2 Parameters
2.2 List of parameters
p1528[0...n]
CI: Torque limit upper scaling / M_max upper scal
CU250D-2_PN_F
Access level: 4
CU250D-2_DP_F
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the scaling of the upper torque limit in p1522.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1529[0...n]
CI: Torque limit lower scaling / M_max lower scal
CU240D-2_DP
Access level: 4
CU240D-2_PN
Can be changed: T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source for the scaling of the lower torque limit in p1523.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1529[0...n]
CI: Torque limit lower scaling / M_max lower scal
CU250D-2_PN_F
Access level: 4
CU250D-2_DP_F
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the scaling of the lower torque limit in p1523.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1530[0...n]
Power limit motoring / P_max mot
Access level: 2
Can be changed: U, T
Unit group: 14_5
Min
0.00 [kW]
Description:
Sets the power limit when motoring.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0500, p1531
Note:
The power limit is limited to 300% of the rated motor power.
224
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
100000.00 [kW]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 6630
Factory setting
2686[0]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 6630
Factory setting
1525[0]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 6630
Factory setting
2686[1]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6640
Factory setting
0.00 [kW]
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313