p0553[0...n]
Brake holding torque / Brake M_hold
Access level: 3
Can be changed: T
Unit group: 7_1
Min
0 [Nm]
Description:
Sets the brake holding torque.
p0554[0...n]
Brake moment of inertia / Brake J
Access level: 3
Can be changed: T
Unit group: -
Min
0 [kgm²]
Description:
Sets the brake moment of inertia.
p0573
Inhibit automatic reference value calculation / Inhibit calc
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Setting to inhibit the calculation of reference parameters (e.g. p2000) when automatically calculating the motor and
closed-loop control parameters (p0340, p3900).
Value:
0:
1:
Notice:
The inhibit for the reference value calculation is canceled when new motor parameters (e.g. p0305) are entered and
only one drive data set exists (p0180 = 1). This is the case during initial commissioning.
Once the motor and control parameters have been calculated (p0340, p3900), the inhibit for the reference value
calculation is automatically re-activated.
Note:
If value = 0:
The automatic calculation (p0340, p3900) overwrites the reference parameters.
If value = 1:
The automatic calculation (p0340, p3900) does not overwrite the reference parameters.
p0580
Measuring probe input terminal / MT input terminal
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the input terminal for the measuring probe for speed actual value measurement.
Value:
0:
21:
23:
Dependency:
Refer to: p0581
Refer to: A07498
Note:
DI: Digital Input
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
No
Yes
No meas probe
DI 1 (X07.2)
DI 3 (X08.2)
Calculated: -
Scaling: -
Unit selection: p0505
Max
340.28235E36 [Nm]
Calculated: -
Scaling: -
Unit selection: -
Max
2147483647 [kgm²]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
23
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0 [Nm]
Data type: Integer32
Dyn. index: MDS
Func. diagram: -
Factory setting
0 [kgm²]
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0