2 Parameters
2.2 List of parameters
Note:
For high moments of inertia, it is practical to scale the runtime of the calibration higher.
p2000
Reference speed reference frequency / n_ref f_ref
Access level: 2
Can be changed: T
Unit group: -
Min
6.00 [rpm]
Description:
Sets the reference quantity for speed and frequency.
All speeds or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The following applies: Reference frequency (in Hz) = reference speed (in ((rpm) / 60) x pole pair number)
Dependency:
This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting using
p0573 = 1.
Refer to: p2001, p2002, p2003, r2004, r3996
Notice:
When the reference speed / reference frequency is changed, short-term communication interruptions may occur.
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
Example 1:
The signal of an analog input (e.g. r0755[0]) is connected to a speed setpoint (e.g. p1070[0]). The actual percentage
input value is cyclically converted into the absolute speed setpoint using the reference speed (p2000).
Example 2:
The setpoint from PROFIBUS (r2050[1]) is connected to a speed setpoint (e.g. p1070[0]). The actual input value is
cyclically converted into a percentage value via the pre-specified scaling 4000 hex. This percentage value is
converted to the absolute speed setpoint via reference speed (p2000).
p2001
Reference voltage / Reference voltage
Access level: 3
Can be changed: T
Unit group: -
Min
10 [Vrms]
Description:
Sets the reference quantity for voltages.
All voltages specified as relative value are referred to this reference quantity. This also applies for direct voltage
values (= rms value) like the DC-link voltage.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Note:
This reference quantity also applies to direct voltage values. It is not interpreted as rms value, but as DC voltage
value.
Dependency:
p2001 is only updated during automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning has been carried
out first for drive data set zero and as a result overwriting of the parameter has not been blocked by setting p0573 =
1.
Refer to: r3996
Notice:
When the reference voltage is changed, short-term communication interruptions may occur.
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
For infeed units, the parameterized device supply voltage (p0210) is pre-assigned as the reference quantity.
Example:
The actual value of the DC link voltage (r0070) is connected to a test socket (e.g. p0771[0]). The actual voltage value
is cyclically converted into a percentage of the reference voltage (p2001) and output according to the parameterized
scaling.
266
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
210000.00 [rpm]
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
100000 [Vrms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
1500.00 [rpm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
1000 [Vrms]
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313