F30809
Power unit: Switching information not valid
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
For 3P gating unit, the following applies:
The last switching status word in the setpoint telegram is identified by the end ID. Such an end ID was not found.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
A30810 (F)
Power unit: Watchdog timer
Message class:
Hardware/software error (1)
Reaction:
NONE
Acknowledge:
NONE
Cause:
When booting it was detected that the cause of the previous reset was an SAC watchdog timer overflow.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
F30850
Power unit: Internal software error
Message class:
Hardware/software error (1)
Reaction:
OFF1 (NONE, OFF2, OFF3)
Acknowledge:
POWER ON
Cause:
An internal software error has occurred in the power unit.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- replace power unit.
- if required, upgrade the firmware in the power unit.
- contact Technical Support.
F30903
Power unit: I2C bus error occurred
Message class:
Hardware/software error (1)
Reaction:
OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
Communications error with an EEPROM or an analog/digital converter.
Fault value (r0949, interpret hexadecimal):
80000000 hex:
- internal software error.
00000001 hex ... 0000FFFF hex:
- module fault.
Remedy:
For fault value = 80000000 hex:
- upgrade firmware to later version.
For fault value = 00000001 hex ... 0000FFFF hex:
- replace the module.
A30920 (F)
Temperature sensor fault
Message class:
Power electronics faulted (5)
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected.
KTY: R > 2120 Ohm, PT1000: R > 2120 Ohm
2: Measured resistance too low.
PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
4 Faults and alarms
4.2 List of faults and alarms
935