F07453
LR: Position actual value preprocessing error
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
An error has occurred during the position actual value preprocessing.
Remedy:
Check the encoder for the position actual value preprocessing.
See also: p2502 (LR encoder assignment)
A07454
LR: Position actual value preprocessing does not have a valid encoder
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
One of the following problems has occurred with the position actual value preprocessing:
- an encoder is not assigned for the position actual value preprocessing (p2502 = 0).
- an encoder an an encoder data set have been assigned, however, the encoder data set does not contain any
encoder data (p0400 = 0) or invalid data (e.g. p0408 = 0).
Remedy:
Check the drive data sets, encoder data sets and encoder assignment.
See also: p0187 (Encoder 1 encoder data set number), p0188 (Encoder 2 encoder data set number), p0400
(Encoder type selection), p2502 (LR encoder assignment)
A07455
EPOS: Maximum velocity limited
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum velocity (p2571) is too high to correctly calculate the modulo correction.
Within the sampling time for positioning (8 ms), with the maximum velocity, a maximum of the half modulo length
must be moved through. p2571 was limited to this value.
Remedy:
Reduce the maximum velocity (p2571).
A07456
EPOS: Setpoint velocity limited
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The actual setpoint velocity is greater than the parameterized maximum velocity (p2571) and is therefore limited.
Remedy:
- check the entered setpoint velocity.
- reduce the velocity override (CI: p2646).
- increase the maximum velocity (p2571).
- check the signal source for the externally limited velocity (CI: p2594).
A07457
EPOS: Combination of input signals illegal
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
An illegal combination of input signals that are simultaneously set was identified.
Alarm value (r2124, interpret decimal):
0: Jog 1 and jog 2 (p2589, p2590).
1: Jog 1 or jog 2 and direct setpoint input/MDI (p2589, p2590, p2647).
2: Jog 1 or jog 2 and start referencing (p2589, p2590, p2595).
3: Jog 1 or jog 2 and activate traversing task (p2589, p2590, p2631).
4: Direct setpoint input/MDI and starting referencing (p2647, p2595).
5: Direct setpoint input/MDI and activate traversing task (p2647, p2631).
6: Start referencing and activate traversing task (p2595, p2631).
Remedy:
Check the appropriate input signals and correct.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
4 Faults and alarms
4.2 List of faults and alarms
871