Changing the fault response for maximum 20 faults <1>
Chng resp F_no
0 ... 65535
p2100 (0)
[0]
0. Fault code
1. Fault code
[1]
19. Fault code
[19]
[19]
Changing the acknowledge mode for maximum 20 faults <1>
Chng ackn F_no
0 ... 65535
p2126 (0)
0. Fault code
[0]
[1]
1. Fault code
[19]
19. Fault code
[19]
<1>
The fault response, acknowledge mode and message type for all faults and alarms are set to meaningful default values in the factory setting.
Changes are only possible in specific value ranges specified by SIEMENS.
When the message type is changed, the supplementary information is tranferred from fault value r0949 to alarm value r2124 and vice versa.
1
2
Diagnostics
Faults/alarms configuration
Chng resp resp
0 ... 6
p2101 (0)
[0]
Fault response
0 = NONE
Fault response
1 = OFF1
[1]
2 = OFF2
3 = OFF3
5 = STOP2
6 = IASC/DCBRK
Fault response
Chng ackn mode
1 ... 2
p2127 (1)
Acknowledge mode
1 = acknowledegment is only possible using POWER ON
[0]
2 = acknowledegment IMMEDIATELY after the cause has been
[1]
Acknowledge mode
removed.
Acknowledge mode
3
4
Changing the message type - fault ”=> alarm for maximum 20 faults/alarms <1>
Chng type msg_no
0 ... 65535
p2118 (0)
[0]
0. Fault/alarm code
1. Fault/alarm code
[1]
19. Fault/alarm code
[19]
5
6
fp_8075_97_51.vsd
09.12.2015
V4.7.6
Change type type
1 ... 3
p2119 (1)
[0]
Fault/alarm type
1 = Fault
Fault/alarm type
[1]
2 = Alarm
3 = No message
Fault/alarm type
[19]
DCBRK = DC Brake
IASC = Internal Armature Short-Circuit
7
Function diagram
SINAMICS G120D
8
- 8075 -