p2291
CO: Technology controller maximum limiting / Tec_ctrl max_lim
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-200.00 [%]
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2292
CO: Technology controller minimum limiting / Tec_ctrl min_lim
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-200.00 [%]
Description:
Sets the minimum limit of the technology controller.
Dependency:
Refer to: p2291
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2293
Technology controller ramp-up/ramp-down time / Tec_ctr t_RU/RD
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
0.00 [s]
Description:
Sets the ramping time for the output signal of the technology controller.
Dependency:
Refer to: p2291, p2292
Note:
The time refers to the set maximum and minimum limits (p2291, p2292).
r2294
CO: Technology controller output signal / Tec_ctrl outp_sig
CU240D-2_DP
Access level: 2
CU240D-2_PN
Can be changed: -
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
- [%]
Description:
Display and connector output for the output signal of the technology controller.
Dependency:
Refer to: p2295
p2295
CO: Technology controller output scaling / Tec_ctrl outp scal
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-100.00 [%]
Description:
Sets the scaling for the output signal of the technology controller.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
100.00 [%]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
0.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
1.00 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
100.00 [%]