Siemens SINAMICS G120D CU240D-2 DP Manual page 144

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0918
PROFIBUS address / PB address
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: T
CU250D-2_DP_F
Unit group: -
Min
1
Description:
Displays or sets the PROFIBUS address for PROFIBUS interface on the Control Unit.
The address can be set as follows:
1) Using the DIP switch on the Control Unit.
--> p0918 can then only be read and displays the selected address.
--> A change only becomes effective after a POWER ON.
2) Using p0918
--> Only if all of the DIP switches are set to ON or OFF.
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
For p0014 = 0, the following applies:
Before a changed setting becomes permanently effective, a non-volatile RAM to ROM data save is required. To do
this, set p0971 = 1 or p0014 = 1.
Note:
Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
p0922
PROFIdrive PZD telegram selection / PZD telegr_sel
CU240D-2_DP
Access level: 1
CU240D-2_PN
Can be changed: C(1), T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
1
Description:
Sets the send and receive telegram.
Value:
1:
20:
350:
352:
353:
354:
999:
Dependency:
Refer to: p2038
Refer to: F01505
Note:
For p0922 = 100 ... 199, p2038 is automatically set to 1 and p2038 can no longer be changed. This means that for
these telegrams, the "SIMODRIVE 611 universal" interface mode is set and cannot be changed.
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited.
The inhibited interconnections can only be changed again after setting value 999.
p0922
PROFIdrive PZD telegram selection / PZD telegr_sel
CU250D-2_PN_F
Access level: 1
CU250D-2_DP_F
Can be changed: C(1), T
Unit group: -
Min
7
Description:
Sets the send and receive telegram.
144
Standard telegram 1, PZD-2/2
Standard telegram 20, PZD-2/6
SIEMENS telegram 350, PZD-4/4
SIEMENS telegram 352, PZD-6/6
SIEMENS telegram 353, PZD-2/2, PKW-4/4
SIEMENS telegram 354, PZD-6/6, PKW-4/4
Free telegram configuration with BICO
Calculated: -
Scaling: -
Unit selection: -
Max
126
Calculated: -
Scaling: -
Unit selection: -
Max
999
Calculated: -
Scaling: -
Unit selection: -
Max
999
Data type: Unsigned16
Dyn. index: -
Func. diagram: 2401, 2410
Factory setting
126
Data type: Unsigned16
Dyn. index: -
Func. diagram: 2401, 2420
Factory setting
1
Data type: Unsigned16
Dyn. index: -
Func. diagram: 2401, 2420
Factory setting
999
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313