Siemens SINAMICS G120D CU240D-2 DP Manual page 864

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
37: Source parameter for a BICO interconnection was not able to be determined.
38: An index was set for a non-indexed (or CDS-dependent) parameter.
39: No index was set for an indexed parameter.
41: A bit operation is only permissible for parameters with the parameter format DISPLAY_BIN.
42: A value not equal to 0 or 1 was set for a BitOperation.
43: Reading the parameter to be changed by the BitOperation was unsuccessful.
51: Factory setting for DEVICE may only be executed on the DEVICE.
61: The setting of a value was unsuccessful.
Remedy:
- check the parameter involved.
- check the macro file and BICO interconnection.
See also: p0015, p1000, p1500
F07083
Macro: ACX file not found
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The ACX file (macro) to be executed was not able to be found in the appropriate directory.
Fault value (r0949, interpret decimal):
Parameter number with which the execution was started.
See also: p0015, p1000, p1500
Remedy:
- check whether the file is saved in the appropriate directory on the memory card.
F07084
Macro: Condition for WaitUntil not fulfilled
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The WaitUntil condition set in the macro was not fulfilled in a certain number of attempts.
Fault value (r0949, interpret decimal):
Parameter number for which the condition was set.
Remedy:
Check and correct the conditions for the WaitUntil loop.
F07086
Units changeover: Parameter limit violation due to reference value change
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A reference parameter was changed in the system. This resulted in the fact that for the parameters involved, the
selected value was not able to be written in the per unit notation.
The values of the parameters were set to the corresponding violated minimum limit/maximum limit or to the factory
setting.
Possible causes:
- the steady-state minimum limit/maximum limit or that defined in the application was violated.
Fault value (r0949, parameter):
Diagnostics parameter to display the parameters that were not able to be re-calculated.
See also: p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004
Remedy:
Check the adapted parameter value and if required correct.
F07088
Units changeover: Parameter limit violation due to units changeover
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A changeover of units was initiated. This resulted in a violation of a parameter limit
Possible causes for the violation of a parameter limit:
- When rounding off a parameter corresponding to its decimal places, the steady-state minimum limit or maximum
limit was violated.
- inaccuracies for the data type "FloatingPoint".
864
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents