Siemens SINAMICS G120D CU240D-2 DP Manual page 210

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
r1454
CO: Speed controller system deviation I component / n_ctrl sys dev Tn
Access level: 4
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Display and connector output for the system deviation of the I component of the speed controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
p1455[0...n]
CI: Speed controller P gain adaptation signal / n_ctr adapt_sig Kp
Access level: 4
Can be changed: T
Unit group: -
Min
-
Description:
Sets the source for the adaptation signal to additionally adapt the P gain of the speed controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1456, p1457, p1458, p1459
p1456[0...n]
Speed controller P gain adaptation lower starting point / n_ctrl AdaptKpLow
Access level: 4
Can be changed: U, T
Unit group: -
Min
0.00 [%]
Description:
Sets the lower starting point of the adaptation range for the additional adaptation of the P gain of the speed controller.
The values are in % and refer to the set source of the adaptation signal.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1455, p1457, p1458, p1459
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
p1457[0...n]
Speed controller P gain adaptation upper starting point / n_ctrl AdaptKp up
Access level: 4
Can be changed: U, T
Unit group: -
Min
0.00 [%]
Description:
Sets the upper starting point of the adaptation range for the additional adaptation of the P gain of the speed
controller.
The values are in % and refer to the set source of the adaptation signal.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Refer to: p1455, p1456, p1458, p1459
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
210
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
400.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
400.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6040
Factory setting
- [rpm]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 6050
Factory setting
0
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6050
Factory setting
0.00 [%]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6050
Factory setting
0.00 [%]
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents