2 Parameters
2.2 List of parameters
r3978
BICO CounterDevice / BICO CounterDevice
Access level: 4
Can be changed: -
Unit group: -
Min
-
Description:
Displays the counter reading for modified BICO interconnections on this device.
The counter is incremented by one for each modified BICO interconnection.
p3981
Faults acknowledge drive object / Faults ackn DO
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Setting to acknowledge all active faults of a drive object.
Notice:
Safety messages cannot be acknowledged using this parameter.
Note:
Parameter should be set from 0 to 1 to acknowledge.
After acknowledgment, the parameter is automatically reset to 0.
p3985
Master control mode selection / PcCtrl mode select
Access level: 3
Can be changed: U, T
Unit group: -
Min
0
Description:
Sets the mode to change over the master control / LOCAL mode.
Value:
0:
1:
Danger:
When changing the master control in operation, the drive can manifest undesirable behavior - e.g. it can accelerate
up to another setpoint.
r3986
Parameter count / Parameter No.
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the number of parameters for this drive unit.
The number comprises the device-specific and the drive-specific parameters.
Dependency:
Refer to: r0980, r0981, r0989
r3988[0...1]
Boot state / Boot_state
Access level: 4
Can be changed: -
Unit group: -
Min
0
Description:
Index 0:
Displays the boot state.
Index 1:
Displays the partial boot state
404
Change master control for STW1.0 = 0
Change master control in operation
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
800
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned8
Dyn. index: -
Func. diagram: 8060
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
-
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313