Warning:
The maximum voltage difference between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
p0757[0...1]
CU analog inputs characteristic value x1 / CU AI char x1
CU240D-2_DP
Access level: 2
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-50.000
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
The parameters for the characteristic do not have a limiting effect.
p0758[0...1]
CU analog inputs characteristic value y1 / CU AI char y1
CU240D-2_DP
Access level: 2
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
The parameters for the characteristic do not have a limiting effect.
p0759[0...1]
CU analog inputs characteristic value x2 / CU AI char x2
CU240D-2_DP
Access level: 2
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-50.000
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V) of the 2nd value pair of the characteristic.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
The parameters for the characteristic do not have a limiting effect.
p0760[0...1]
CU analog inputs characteristic value y2 / CU AI char y2
CU240D-2_DP
Access level: 2
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
The parameters for the characteristic do not have a limiting effect.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Calculated: -
Scaling: -
Unit selection: -
Max
160.000
Calculated: -
Scaling: -
Unit selection: -
Max
1000.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
160.000
Calculated: -
Scaling: -
Unit selection: -
Max
1000.00 [%]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9566, 9568, 9576
Factory setting
0.000
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9566, 9568, 9576
Factory setting
0.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9566, 9568, 9576
Factory setting
10.000
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9566, 9568, 9576
Factory setting
100.00 [%]
125