Signal sources for ZSW3 im Interface Mode SINAMICS
Signal
ZSW3.0
1 = DC braking active
ZSW3.1
1 = |n_act| > p1226 (n_standstill)
ZSW3.2
1 = |n_act| > p1080 (n_min)
1 = I_act p2170
ZSW3.3
ZSW3.4
1 = |n_act| > p2155
1 = |n_act| p2155
ZSW3.5
1 = |n_act| r1119 (n_set)
ZSW3.6
1 = Vdc p2172
ZSW3.7
ZSW3.8
1 = Vdc > p2172
ZSW3.9
1 = Ramping finished
ZSW3.10
1 = Technology controller output at the lower limit
ZSW3.11
1 = Technology controller output at the upper limit
ZSW3.12
Reserved
ZSW3.13
Reserved
ZSW3.14
Reserved
ZSW3.15
Reserved
<1>
Used in telegram 350.
1
2
PROFIdrive (PROFIBUS/PROFINET), EtherNet/IP
PROFIdrive - ZSW3 status word interconnection
Meaning
3
4
Interconnection
[Function diagram]
[Function diagram]
parameters
internal status word
signal source
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
p2051[3] = r0053
[2511.7]
[2511.7]
[2511.7]
[2511.7]
-
-
-
-
5
6
Function diagram
fp_2456_97_61.vsd
G120D CU250D-2
09.12.2015
V4.7.6
<1>
Inverted
[7017.5]
-
[2534.7]
-
[2534.7]
-
[2534.7]
-
[2534.7]
-
[2534.7]
-
[2534.7]
-
[2534.7]
-
[2534.7]
-
[3080.7]
-
[7958.7]
-
[7958.7]
-
-
-
-
-
-
-
-
-
7
8
- 2456 -