Siemens SINAMICS G120D CU240D-2 DP Manual page 87

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

For bit 02:
If the bit is set, in the event of a deviation less than the tolerance window for the zero mark (p4681, p4682), the
pulses per revolution are corrected. If the bit is not set, encoder fault F3x131 is triggered.
For bits 05, 04:
The actual hardware only supports 1x or 4x signal evaluation.
Bit 5/4 = 0/0: Signal evaluation per period, 4x.
Bit 5/4 = 1/0: Illegal setting.
Bit 5/4 = 0/1: Signal evaluation per period, 1x.
Bit 5/4 = 1/1: Illegal setting.
For bit 06:
If the function is active, when dn/dt monitoring responds, the speed actual value is internally frozen for a time
equivalent to two current controller clock cycles. The rotor position continues to be integrated. The actual value is
then re-enabled after this time has expired.
For bit 11:
If the bit is set, the Sensor Module checks within a certain time grid whether the fault cause is still present. This
enables the Sensor Module to switch from the fault state to the operating state and provide valid actual values
automatically. The faults are displayed until the user acknowledges them.
For bit 12:
Additional fault messages can be activated for extended fault diagnostics.
For bit 13:
When the bit is set, for an incremental encoder with zero mark, the absolute value in Gn_XIST2 can be requested via
Gn_STW.13. The absolute value is only valid after passing the zero mark.
For bit 26:
Track monitoring is de-activated for the square-wave encoders when the bit is set, even if the monitoring function is
selected in p0405.2.
p0438[0...n]
Squarewave encoder filter time / Enc t_filt
Access level: 3
Can be changed: C(4)
Unit group: -
Min
0.00 [µs]
Description:
Sets the filter time for a squarewave encoder.
The hardware of the squarewave encoder only supports the following values:
0: No filtering
0.04 µs
0.64 µs
2.56 µs
10.24 µs
20.48 µs
Dependency:
Refer to: r0452
Notice:
If the filter time is too long, the track signals A/B/R may be suppressed and the appropriate messages output.
Note:
The most suitable filter time depends on the number of pulses and maximum speed of the square-wave encoder.
The filter time is automatically corrected to the next value when entering a non-specified value. In this case, no
message is output.
The effective filter time is displayed in r0452.
p0439[0...n]
Encoder ramp-up time / Enc ramp-up time
Access level: 3
Can be changed: C(4)
Unit group: -
Min
0 [ms]
Description:
Sets the ramp-up time for the encoder.
The encoder supplies stable track signals once this time has elapsed.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [µs]
Calculated: -
Scaling: -
Unit selection: -
Max
65535 [ms]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: EDS, p0140
Func. diagram: -
Factory setting
0.64 [µs]
Data type: Unsigned16
Dyn. index: EDS, p0140
Func. diagram: -
Factory setting
0 [ms]
87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents