A07852 (F)
External alarm 3
Message class:
External measured value / signal state outside the permissible range (16)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The condition for "External alarm 3" is satisfied.
Note:
The "External alarm 3" is initiated by a 1/0 edge via binector input p2117.
See also: p2117 (External alarm 3)
Remedy:
Eliminate the causes of this alarm.
F07860 (A)
External fault 1
Message class:
External measured value / signal state outside the permissible range (16)
Reaction:
OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The condition for "External fault 1" is satisfied.
Note:
The "External fault 1" is initiated by a 1/0 edge via binector input p2106.
See also: p2106 (External fault 1)
Remedy:
- eliminate the causes of this fault.
- acknowledge fault.
F07861 (A)
External fault 2
Message class:
External measured value / signal state outside the permissible range (16)
Reaction:
OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The condition for "External fault 2" is satisfied.
Note:
The "External fault 2" is initiated by a 1/0 edge via binector input p2107.
See also: p2107 (External fault 2)
Remedy:
- eliminate the causes of this fault.
- acknowledge fault.
F07862 (A)
External fault 3
Message class:
External measured value / signal state outside the permissible range (16)
Reaction:
OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The condition for "External fault 3" is satisfied.
Note:
The "External fault 3" is initiated by a 1/0 edge via the following parameters.
- AND logic operation, binector input p2108, p3111, p3112.
- switch-on delay p3110.
See also: p2108 (External fault 3), p3110 (External fault 3 switch-on delay), p3111 (External fault 3 enable), p3112
(External fault 3 enable negated)
Remedy:
- eliminate the causes of this fault.
- acknowledge fault.
A07891
Drive: Load monitoring pump/fan blocked
Message class:
Motor overload (8)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The load monitoring is configured for a pump or fan (p2193 = 4, 5).
The monitoring function detects when the pump/fan is blocked.
It is possible that the blocking torque threshold (p2168) is set too low (e.g. heavy duty starting).
See also: p2181 (Load monitoring response), p2193 (Load monitoring configuration)
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
4 Faults and alarms
4.2 List of faults and alarms