Siemens SINAMICS G120D CU240D-2 DP Manual page 72

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0360[0...n]
Motor magnetizing inductance / Mot Lh
Access level: 3
Can be changed: C(3), U, T
Unit group: -
Min
0.00000 [mH]
Description:
Sets the magnetizing inductance of the motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor
identification routine (p1910).
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2).
p0362[0...n]
Motor saturation characteristic flux 1 / Mot saturat.flux 1
Access level: 4
Can be changed: C(3), U, T
Unit group: -
Min
10.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 1st value pair of the characteristic.
Sets the first flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0366
Note:
For induction motors, p0362 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0363[0...n]
Motor saturation characteristic flux 2 / Mot saturat.flux 2
Access level: 4
Can be changed: C(3), U, T
Unit group: -
Min
10.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 2nd value pair of the characteristic.
Sets the second flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0367
Note:
For induction motors, p0363 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0364[0...n]
Motor saturation characteristic flux 3 / Mot saturat.flux 3
Access level: 4
Can be changed: C(3), U, T
Unit group: -
Min
10.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
72
Calculated: p0340 = 1,2
Scaling: -
Unit selection: -
Max
10000.00000 [mH]
Calculated: -
Scaling: -
Unit selection: -
Max
800.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
800.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
800.0 [%]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 6727
Factory setting
0.00000 [mH]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 6723
Factory setting
60.0 [%]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 6723
Factory setting
85.0 [%]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 6723
Factory setting
115.0 [%]
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents