p2150[0...n]
Hysteresis speed 3 / n_hysteresis 3
Access level: 3
Can be changed: U, T
Unit group: 3_1
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency:
Refer to: p2161, r2197, r2199
p2151[0...n]
CI: Speed setpoint for messages/signals / n_set for msg
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency:
Refer to: r2197, r2198, r2199
p2152[0...n]
Delay for comparison n > n_max / Del n > n_max
Access level: 3
Can be changed: U, T
Unit group: -
Min
0 [ms]
Description:
Sets the delay time for comparing the speed with the maximum speed.
Dependency:
Refer to: p1082, r1084, r1087, p2162
p2153[0...n]
Speed actual value filter time constant / n_act_filt T
Access level: 3
Can be changed: U, T
Unit group: -
Min
0 [ms]
Description:
Sets the time constant of the PT1 element to smooth the speed / velocity actual value.
The smoothed actual speed/velocity is compared with the threshold values and is only used for messages and
signals.
Dependency:
Refer to: r2169
p2155[0...n]
Speed threshold 2 / n_thresh val 2
Access level: 3
Can be changed: U, T
Unit group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the following messages:
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
300.00 [rpm]
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
1000000 [ms]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010, 8011, 8022
Factory setting
2.00 [rpm]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 8011
Factory setting
1170[0]
Data type: Unsigned16
Dyn. index: DDS, p0180
Func. diagram: 8023
Factory setting
200 [ms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010
Factory setting
0 [ms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010
Factory setting
900.00 [rpm]