Siemens SINAMICS G120D CU240D-2 DP Manual page 129

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

p0802
Data transfer: memory card as source/target / mem_card src/targ
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Sets the number for data transfer of a parameter backup from/to memory card.
Transfer from memory card to device memory (p0804 = 1):
- sets the source of parameter backup (e.g. p0802 = 48 --> PS048xxx.ACX is the source).
Transfer from non-volatile device memory to memory card (p0804 = 2):
- sets the target of parameter backup (e.g. p0802 = 23 --> PS023xxx.ACX is the target).
Dependency:
Refer to: p0803, p0804
Note:
The volatile device memory is not influenced by data transfer.
p0803
Data transfer: device memory as source/target / Dev_mem src/targ
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Sets the number for data transfer of a parameter backup from/to the non-volatile device memory.
Transfer from memory card to device memory (p0804 = 1):
- sets the target of the parameter backup (e.g. p0803 = 10 --> PS010xxx.ACX is the target).
Transfer from non-volatile device memory to memory card (p0804 = 2):
- sets the source of the parameter backup (e.g. p0803 = 11 --> PS011xxx.ACX is the source).
Value:
0:
10:
11:
12:
30:
Dependency:
Refer to: p0802, p0804
Note:
The volatile device memory is not influenced by data transfer.
p0804
Data transfer start / Data transf start
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Sets the transfer direction and start of data transfer between the memory card and non-volatile device memory.
Example 1:
The parameter backup is to be transferred from the non-volatile device memory to the memory card with setting 0.
The parameter backup is to be stored on the memory card with setting 22.
p0802 = 22 (parameter backup stored on memory card as target with setting 22)
p0803 = 0 (parameter backup stored in device memory as source with setting 0)
p0804 = 2 (start data transfer from device memory to memory card)
--> PS000xxx.ACX is transferred from device memory to memory card and stored as PS022xxx.ACX.
--> the parameter backup PS022xxx.ACX on the memory card can be used for data backup.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Source/target standard
Source/target with setting 10
Source/target with setting 11
Source/target with setting 12
Source/target with setting 30
Calculated: -
Scaling: -
Unit selection: -
Max
100
Calculated: -
Scaling: -
Unit selection: -
Max
30
Calculated: -
Scaling: -
Unit selection: -
Max
1100
2 Parameters
2.2 List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
129