X10.3
(X10.4)
AI 0/1
+
<1>
X10.7
(X10.7)
<3>
-10 ... +10 V
<1>
Differential Input!
For an input signal referred to ground, terminal X10.7 must be connected to reference potential M.
Notice:
The voltage between inputs and between input and the ground point must not exceed 35 V. If this is not observed, the input will be damaged.
<2>
Possible settings p0756[0] and p0756[1]:
= 0: Unipolar voltage input (0 V ... +10 V)
= 8: No sensor connected
<3>
Values in brackets --> AI 1
1
2
Input/Output Terminals
Analog inputs 0 ... 1 (AI 0 ... AI 1)
<2>
CU AI type
0 ... 8
p0756[0..1] (0)
Hardware smoothing
100 µs
A
Type switching
Analog input
D
CU AI sim setp
-50.000 ... 2000.000
p0798[0..1] (0.000)
3
4
CU AI U/I_inp act
r0752
CU AI char x1
-50.000 ... 160.000
p0757[0..1] (0.000)
CU AI sim_mode
0 ... 1
p0797[0..1] (0)
CU AI char y2
-1000.00 ... 1000.00 [%]
p0760[0..1] (100.00)
0
x
CU AI char y1
1
-1000.00 ... 1000.00 [%]
p0758[0..1] (0.00)
Reference quantities
CU AI value in % [%]
p2000 ... r2004
r0755
[0..1]
5
6
fp_2251_97_04.vsd
09.12.2015
V4.7.6
CU AI char x2
-50.000 ... 160.000
p0759[0..1] (10.000) CU AI T_smooth
0.0 ... 1000.0 [ms]
p0753[0..1] (0.0)
y
[%]
y
2
[%]
y
x
x
x
2
1
y
1
Scaling
x
1
y
x
x
2
x
• x
1
2
100 %
Sampling time of the AI: 4 ms
7
8
Function diagram
- 2251 -