Siemens SINAMICS G120D CU240D-2 DP Manual page 249

Sinamics g120d cu240d-2 series; sinamics g120d cu250d-2 series
Hide thumbs Also See for SINAMICS G120D CU240D-2 DP:
Table of Contents

Advertisement

Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
r1797[0...n]
Motor model kT adaptation corrective value / MotMod kT corr
Access level: 4
Can be changed: -
Unit group: -
Min
- [Nm/A]
Description:
Displays the corrective value of the kT adaptation of the motor model for a permanent-magnet synchronous motor
(PMSM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0826, p1780
Note:
The display of the inactive data sets is only updated when changing over the data set.
p1800[0...n]
Pulse frequency setpoint / Pulse freq setp
Access level: 2
Can be changed: U, T
Unit group: -
Min
2.000 [kHz]
Description:
Sets the pulse frequency for the converter.
This parameter is pre-set to the rated converter value when the drive is first commissioned.
Dependency:
Refer to: p0230
Note:
The maximum and minimum possible pulse frequency is also determined by the power unit being used (minimum
pulse frequency: 2 kHz or 4 kHz).
When the pulse frequency is increased, depending on the particular power unit, the maximum output current can be
reduced (derating, refer to r0067).
If a sine-wave filter is parameterized as output filter (p0230 = 3), then the pulse frequency cannot be set below the
minimum value required for the filter.
For operation with output reactors, the pulse frequency is limited to 4 kHz (see p0230).
If p1800 is changed during commissioning (p0010 > 0), then it is possible that the old value will no longer be able to
be set. The reason for this is that the dynamic limits of p1800 have been changed by a parameter that was set when
the drive was commissioned (e.g. p1082).
r1801[0...1]
CO: Pulse frequency / Pulse frequency
Access level: 2
Can be changed: -
Unit group: -
Min
- [kHz]
Description:
Display and connector output for the actual converter switching frequency.
Index:
[0] = Actual
[1] = Modulator minimum value
Note:
The selected pulse frequency (p1800) may be reduced if the drive converter has an overload condition (p0290).
p1802[0...n]
Modulator mode / Modulator mode
Access level: 3
Can be changed: T
Unit group: -
Min
0
Description:
Sets the modulator mode.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Calculated: -
Scaling: -
Unit selection: -
Max
- [Nm/A]
Calculated: -
Scaling: -
Unit selection: -
Max
16.000 [kHz]
Calculated: -
Scaling: p2000
Unit selection: -
Max
- [kHz]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
4
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6731
Factory setting
- [Nm/A]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8021
Factory setting
4.000 [kHz]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [kHz]
Data type: Integer16
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
4
249

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu250d-2 pn-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-fSinamics g120d cu250d-2 dp-f

Table of Contents