- check and correct the phase assignment at the power unit.
- check the line supply phases.
See also: p0210 (Drive unit line supply voltage)
F30003
Power unit: DC link voltage undervoltage
Message class:
Infeed faulted (13)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected an undervoltage condition in the DC link.
- line supply failure
- line supply voltage below the permissible value.
- line phase interrupted.
Note:
The monitoring threshold for the DC link undervoltage is the minimum of the following values:
- for a calculation, refer to p0210.
Remedy:
- check the line supply voltage
- check the line supply phases.
See also: p0210 (Drive unit line supply voltage)
F30004
Power unit: Overtemperature heat sink AC inverter
Message class:
Power electronics faulted (5)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature of the power unit heat sink has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- pulse frequency too high.
Fault value (r0949, interpret decimal):
Temperature [1 bit = 0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- reduce the pulse frequency if this is higher than the rated pulse frequency.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
See also: p1800 (Pulse frequency setpoint)
F30005
Power unit: Overload I2t
Message class:
Power electronics faulted (5)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit was overloaded (r0036 = 100 %).
- the permissible rated power unit current was exceeded for an inadmissibly long time.
- the permissible load duty cycle was not maintained.
Fault value (r0949, interpret decimal):
I2t [100 % = 16384].
Remedy:
- reduce the continuous load.
- adapt the load duty cycle.
- check the motor and power unit rated currents.
- reduce the current limit (p0640).
- during operation with U/f characteristic: reduce the integral time of the current limiting controller (p1341).
See also: r0036 (Power unit overload I2t), r0206 (Rated power unit power), p0307 (Rated motor power)