2 Parameters
2.2 List of parameters
p2247[0...n]
Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
CU240D-2_DP
Access level: 2
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
0.0 [s]
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2248
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
p2248[0...n]
Technology controller motorized potentiometer ramp-down time /
Tec_ctrMop t_rdown
CU240D-2_DP
Access level: 2
CU240D-2_PN
Can be changed: U, T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
0.0 [s]
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2247
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
r2250
CO: Technology controller motorized potentiometer setpoint after RFG /
Tec_ctr mop aftRFG
CU240D-2_DP
Access level: 2
CU240D-2_PN
Can be changed: -
CU240D-2_DP_F
Unit group: 9_1
CU240D-2_PN_F
Min
- [%]
Description:
Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency:
Refer to: r2245
p2251
Technology controller mode / Tec_ctrl mode
CU240D-2_DP
Access level: 3
CU240D-2_PN
Can be changed: T
CU240D-2_DP_F
Unit group: -
CU240D-2_PN_F
Min
0
Description:
Sets the mode for using the technology controller output.
Value:
0:
1:
Dependency:
p2251 = 0, 1 is only effective if the enable signal of the technology controller is interconnected (p2200 > 0).
320
Technology controller as main speed setpoint
Technology controller as supplementary speed setpoint
Calculated: -
Scaling: -
Unit selection: -
Max
1000.0 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.0 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7954
Factory setting
10.0 [s]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 7954
Factory setting
10.0 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7954
Factory setting
- [%]
Data type: Integer16
Dyn. index: -
Func. diagram: 7958
Factory setting
0
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313