p1901
Test pulse evaluation configuration / Test puls config
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the configuration for the test pulse evaluation.
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Recommendation:
If the ground fault test is incorrectly initiated because the motor is not at a complete standstill, then the pulse
cancellation delay time (p1228) should be increased.
Bit field:
Bit
00
01
02
Dependency:
The ground fault test is only possible when the motor is stationary, and is therefore only realized when flying restart is
de-activated (p1200 = 0).
Refer to: p0287
Note:
If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
For bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), it is not repeated.
For bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
r1902
Test pulse evaluation status / Test puls ev stat
Access level: 4
Can be changed: -
Unit group: -
Min
-
Description:
Displays the status of the test pulse evaluation.
Bit field:
Bit
00
01
02
03
04
Note:
If the ground fault test was selected, but not successfully performed, then sufficient current was not be able to be
established during the test pulses.
For bit 04:
A test pulse longer than one sampling time has occurred
p1909[0...n]
Motor data identification control word / MotID STW
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the configuration for the motor data identification.
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Signal name
Phase short-circuit test pulse active
Ground fault detection test pulse active
Test pulse at each pulse enable
Signal name
Short-circuit test successfully performed
Phase short-circuit detected
Ground fault test successfully performed
Ground fault detected
Identification pulse width greater than the
minimum pulse width
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0000 bin
0 signal
No
No
No
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
No
No
No
No
No
Data type: Unsigned32
Dyn. index: MDS
Func. diagram: -
Factory setting
0000 0000 0000 0000 0000 0000 0000
0000 bin
FP
-
-
-
FP
-
-
-
-
-
255