2 Parameters
2.2 List of parameters
p0724
CU digital inputs debounce time / CU DI t_debounce
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.000 [ms]
Description:
Sets the debounce time for digital inputs.
Note:
The digital inputs are read in cyclically every 2 ms (DI 11, DI 12 every 4 ms).
To debounce the signals, the set debounce time is converted into integer multiple debounce clock cycles Tp (Tp =
p0724 / 2 ms).
DI: Digital Input
p0730
BI: CU signal source for terminal DO 0 / CU S_src DO 0
Access level: 2
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for terminal DO 0 (X05.4)
Recommendation:
r0052.0 Ready for switching on
r0052.1 Ready for operation
r0052.2 Operation enabled
r0052.3 Fault present
r0052.4 Coast down active (OFF2)
r0052.5 Quick stop active (OFF3)
r0052.6 Switching-on inhibited active
r0052.7 Alarm present
r0052.9 Control request
r0052.14 Motor rotates forwards
r0053.0 DC braking active
r0053.1 n_act > p2167 (n_off)
r0053.2 n_act <= p1080 (n_min)
r0053.3 I_act > p2170
r0053.4 n_act > p2155
r0053.5 n_act <= p2155
r0053.6 n_act >= n_set
r0053.10 Technology controller output at the lower limit
r0053.11 Technology controller output at the upper limit
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
DO: Digital Output
p0731
BI: CU signal source for terminal DO 1 / CU S_src DO 1
Access level: 2
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for terminal DO 1 (X05.2)
Recommendation:
r0052.0 Ready for switching on
r0052.1 Ready for operation
r0052.2 Operation enabled
r0052.3 Fault present
r0052.4 Coast down active (OFF2)
122
Calculated: -
Scaling: -
Unit selection: -
Max
20.000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
4.000 [ms]
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 2201, 2241
Factory setting
52.3
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 2201, 2241
Factory setting
52.7
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313