4 Faults and alarms
4.2 List of faults and alarms
Fault value (r0949, interpret decimal):
1: Monitoring function SLP not supported (p9501.1).
2: Monitoring function SCA not supported (p9501.7 and p9501.8 ... 15).
3: Monitoring function SLS override not supported (p9501.5).
4: Monitoring function external ESR activation not supported (p9501.4).
5: Monitoring function F-DI in PROFIsafe not supported (p9501.30).
6: Enable actual value synchronization not supported (p9501.3).
9: Monitoring function not supported by the firmware or enable bit not used.
11: Only encoderless monitoring functions integrated in the drive are supported.
12: Safety Integrated for SINUMERIK is not supported on this Control Unit.
20: Motion monitoring functions integrated in the drive are only supported in conjunction with PROFIsafe
(p9501/p9601.1 ... 2 and p9801.1 ... 2).
21: PROFIsafe only supported in conjunction with motion monitoring functions integrated in the drive (p9501/p9601.1
... 2 and p9801.1 ... 2).
23: CU240 does not support monitoring functions requiring an encoder.
25: Drive-integrated motion monitoring functions not supported (p9501, p9601.2).
28: Encoderless monitoring functions are not supported for synchronous motors (p9507.2).
Remedy:
Deselect the monitoring function involved (p9501, p9601, p9801).
Note:
SCA: Safe Cam
SDI: Safe Direction (safe motion direction)
SLP: Safely Limited Position
SLS: Safely Limited Speed
See also: p9501 (SI Motion enable safety functions (Control Unit)), r9771 (SI common functions (processor 1))
F01683
SI Motion P1 (CU): SLS enable missing
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The safety-relevant function "SLS" is not enabled in p9501 although other safety-relevant monitoring functions are
enabled.
Note:
This fault does not result in a safety stop response.
Remedy:
Enable the function "SLS" (p9501.0) and carry out a POWER ON.
Note:
Save the changes before POWER ON (copy from RAM to ROM).
SLS: Safely Limited Speed
See also: p9501 (SI Motion enable safety functions (Control Unit))
F01690
SI Motion: Data save problem for the NVRAM
Message class:
Hardware/software error (1)
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
POWER ON
Cause:
There is not sufficient memory space in the NVRAM on the drive to save parameters r9781 and r9782 (safety
logbook).
Note:
This fault does not result in a safety stop response.
Fault value (r0949, interpret decimal):
0: There is no physical NVRAM available in the drive.
1: There is no longer any free memory space in the NVRAM.
Remedy:
For fault value = 0:
- use a Control Unit NVRAM.
For fault value = 1:
- deselect functions that are not required and that take up memory space in the NVRAM.
- contact Technical Support.