p1015[0...n]
CO: Fixed speed setpoint 15 / n_set_fixed 15
Access level: 2
Can be changed: U, T
Unit group: 3_1
Min
-210000.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 15.
Dependency:
Refer to: p1020, p1021, p1022, p1023, r1024, r1197
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1016
Fixed speed setpoint select mode / n_set_fix select
Access level: 2
Can be changed: T
Unit group: -
Min
1
Description:
Sets the mode to select the fixed speed setpoint.
Value:
1:
2:
Note:
For p1016 = 1:
In this mode, the setpoint is entered via the fixed speed setpoints p1001 ... p1004.
Up to 16 different setpoints are obtained by adding the individual fixed speed setpoints.
For p1016 = 2:
In this mode, the setpoint is entered via the fixed speed setpoints p1001 ... p1015.
p1020[0...n]
BI: Fixed speed setpoint selection Bit 0 / n_set_fixed Bit 0
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for selecting the fixed speed setpoint.
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1021, p1022, p1023, r1197
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
p1021[0...n]
BI: Fixed speed setpoint selection Bit 1 / n_set_fixed Bit 1
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for selecting the fixed speed setpoint.
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1020, p1022, p1023, r1197
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
Direct
Binary
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
2
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3010
Factory setting
0.000 [rpm]
Data type: Integer16
Dyn. index: -
Func. diagram: 3010, 3011
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2505, 3010, 3011
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2505, 3010, 3011
Factory setting
0