General Specifications - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

3.
SPECIFICATIONS

3.1 General Specifications

Item
Display section
Operating ambient
Other than
temperature
display section
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
*1
Operating altitude
*2
Overvoltage category
*3
Pollution degree
Cooling method
Grounding
*1
Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this
instruction may cause a malfunction.
When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high pressure. As a result,
the touch panel may be difficult to press, and the sheet may be peeled off.
*2
This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical
power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the raged voltage of 300V is 2500V.
*3
This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
0 to 40
0 to 40
-20 to 60
10 to 90% RH, non-condensing
10 to 90% RH, non-condensing
Under
Conforms to
intermittent
JIS B3502 and
vibration
IEC61131-2
Under
continuous
vibration
Compliant with JIS B3502, IEC 61131-2 (147m/s
duration)
Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electro
conductive dust particles and must be no direct sunlight. (Same as for saving)
2000m (6562 ft) max.
II or less
2 or less
Self-cooling
Class D grounding (100Ω or less),
To be connected to the panel when grounding is not possible.
Specifications
Frequency
Acceleration
Half-amplitude Sweep Count
5 to 8.4Hz
-
2
8.4 to 150Hz
9.8m/s
5 to 8.4Hz
-
8.4 to 150Hz
2
4.9m/s
2
, 3 times each in X, Y and Z directions, 11ms
3. SPECIFICATIONS
3.1 General Specifications
10 times each
3.5mm
in X, Y and Z
-
directions
1.75mm
-
-
3 - 1
1
2
3
4
5
6
7
8

Advertisement

Table of Contents
loading