General Specifications; Gt27, Gt25-W, Gt25-S, Gt25-V - Mitsubishi Electric GOT2000 Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

3.1

General Specifications

The following shows the general specifications of the GOT.
3.1.1

GT27, GT25-W, GT25-S, GT25-V

Item
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
*6
Operating atmosphere
*3
Operating altitude
Installation location
*4
Overvoltage category
*5
Pollution degree
Cooling method
Grounding
*1
*2
*3
*4
*5
*6
Some models have ANSI/ISA12.12.01 approval for use in Class I, Division 2 (ANSI/ISA 12.12.01, C22.2 No.213-M1987)
*7
When GT2505 is installed vertically, the operating ambient temperature must be between 0°C and 50°C.
*8
Only for GT2505-V, the absolute humidity must not exceed 90% at 40°C if the ambient temperature exceeds 40°C.
3 - 2

3.1 General Specifications

*1
Compliant with
JIS B 3502 and
IEC 61131-2
Compliant with JIS B 3502 and IEC 61131-2 (147 m/s
No greasy fumes, corrosive gas, flammable gas, excessive conductive dust,
Grounding with a ground resistance of 100 Ω or less by using a ground cable that has a cross-sectional area of
Includes the temperature inside the enclosure of the control panel on which the GOT is installed.
When any of the following units is mounted, the maximum operating ambient temperature must be 5°C lower than the one
described in the general specifications.
GT27:
Multimedia unit (GT27-MMR-Z)
MELSECNET/H communication unit (GT15-J71LP23-25, GT15-J71BR13)
CC-Link communication unit (GT15-J61BT13)
GT25 (Except for GT25-W, GT2505-V):
MELSECNET/H communication unit (GT15-J71LP23-25, GT15-J71BR13)
CC-Link communication unit (GT15-J61BT13)
Do not use or store the GOT under a pressure higher than the atmospheric pressure at altitude 0 m.
Doing so may cause a malfunction.
Air purging by applying pressure to the control panel may create clearance between the surface sheet and the touch panel. This
may cause the touch panel to be not sensitive enough or the sheet to come off.
This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical
power distribution network and the machinery within the premises.
Category II applies to equipment that is supplied with power from fixed facilities.
The withstand surge voltage for the equipment with the rated voltage up to 300 V is 2500 V.
This indicates the occurrence rate of conductive material in an environment where a device is used. Pollution degree 2 indicates
an environment where only non-conductive pollution occurs normally and a temporary conductivity caused by condensation shall
be expected depending on the conditions.
hazardous locations. For the details, please contact your local sales office.
Specifications
0 °C to 55 °C
-20°C to 60°C
10% RH to 90% RH, non-condensing
10% RH to 90% RH, non-condensing
Frequency
Under
5 to 8.4 Hz
intermittent
8.4 to 150 Hz
vibration
Under
5 to 8.4 Hz
continuous
8.4 to 150 Hz
vibration
and direct sunlight (as well as at storage)
2000 m or less
Inside control panel
II or less
2 or less
Self-cooling
2 mm
If impossible, connect the ground cable to the control panel.
*2*7
*8
*8
Acceleration
Half amplitude
-
3.5 mm
9.8 m/s2
-
-
1.75 mm
4.9 m/s2
-
2
(15G), 3 times in each X, Y, or Z direction)
2
or more.
Sweep count
10 times in each
X, Y, or Z