3. SPECIFICATIONS

3.1 General Specifications

Item
Display
Operating
section
ambient
Other than
temperature
display section
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
*2
Operating altitude
Installation location
*3
Overvoltage category
*4
Pollution degree
Cooling method
Grounding
*1 : STN liquid crystal type to be stored at or below 39
*2 : Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.). Failure
to observe this instruction may cause a malfunction.
When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high
pressure. As a result, the touch panel may be difficult to press, and the sheet may be peeled off.
*3 : This indicates the section of the power supply to which the equipment is assumed to be connected between the
public electrical power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V.
*4 : This index indicates the degree to which conductive pollution is generated in the environment where the
equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to
condensation.
*5 : When a protective cover for oil is mounted on the GOT, the maximum operating ambient temperature must be
5°C lower than the one described above.
0 to 50
0 to 55
*5
(when horizontally installed), 0 to 50
-20 to 60
*1
10 to 90% RH, non-condensing
*1
10 to 90% RH, non-condensing
Compliant
Under
with JIS
intermittent
B3502 and
vibration
IEC61131-2
Under
continuous
vibration
Compliant with JIS B3502, IEC 61131-2 (147 m/s
directions)
Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of
electro conductive dust particles and must be no direct sunlight. (Same as for saving)
2000 m (6562 ft) max.
Inside control panel
II or less
2 or less
Self-cooling
Class D grounding (100 or less), To be connected to the panel when grounding is not
possible
Specifications
(when vertically installed)
Frequency
Acceleration
5 to 9Hz
-
2
9 to 150Hz
9.8m/s
5 to 9Hz
-
9 to 150Hz
2
4.9m/s
2
, 3 times each in X, Y and Z
WBT.
3.1 General Specifications
Half-
Sweep Count
amplitude
3.5mm
-
10 times each
in X, Y and Z
1.75mm
directions
-
3 - 1
1
2
3
4
5
6
7
8

Advertisement