Plc Side Setting - Mitsubishi Electric GOT2000 Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000:
Table of Contents

Advertisement

4.2.11

PLC Side Setting

POINT
POINT
POINT
OMRON PLC
For details of OMRON PLCs, refer to the following
manuals.
OMRON PLC user's Manual
Model name
PLC CPU
RS-232C adapter
Connection cable
Rack type host link unit
Serial communication module
Communication board
Serial communication board
RS-422A/485 Option board
RS-422A converter
4 - 22
4. CONNECTION TO OMRON PLC
4.2 Serial Connection
Refer to
CPM2A
4.2.12
CQM1, CQM1H
CS1, CJ1, CJ2
4.2.13
CP1H, CP1L, CP1E
4.2.13
4.2.12
C200H
CV500, CV1000,
4.2.14
CV2000, CVM1
CPM1-CIF01, CPM2C-
4.2.12
CIF01-V1
CQM1-CIF01
CQM1-CIF02
4.2.15
CPM2C-CN111
C200H-LK201-V1
4.2.16
C200H-LK202-V1
4.2.16
C500-LK201-V1
4.2.16
CJ1W-SCU21
CJ1W-SCU41
CJ1W-SCU21-V1
CJ1W-SCU31-V1
4.2.17
CJ1W-SCU41-V1
CS1W-SCU21
CS1W-SCU21-V1
C200HW-COM02
C200HW-COM03
4.2.18
C200HW-COM05
C200HW-COM06
CQM1-SCB41
4.2.18
CS1W-SCB21
CS1W-SCB21-V1
4.2.19
CS1W-SCB41
CS1W-SCB41-V1
CP1W-CIF11
4.2.20
CP1W-CIF12
CJ1W-CIF11
4.2.21
4.2.12 Connecting to CPM2A, CQM1,
CQM1H, C200H or RS-232C
adapter
Device settings
Write the following set values to devices of each PLC
CPU and initialize each port using a peripheral tool or
DM monitor.
Device name
DM6645
b15 to b8
2)
1) RS-232C port transmission speed setting
02
: 4800bps
H
03
: 9600bps
H
04
: 19200bps
H
DM6646
2) RS-232C port communication frame format
03
(fixed): The settings are:
H
DM6647
*3
DM6648
DM6649
*1
Only transmission speeds available on the GOT side are
shown.
*2
Set the same transmission speed of the RS-232C port as
that of the GOT side.
*3
Set the RS-232C port host link station No. according to the
Host Address on the GOT side.
HINT
HINT
HINT
Precautions for changing device values
Before changing the device values, make sure that the
switch settings have been changed as follows:
CPM2A:
The communication condition switch to "individual"
Other PLC CPU:
Front panel DIP switch SW5 to "OFF"
Set value
0001
(fixed)
H
b7 to b0
1)
Start bit
: 1 bit
Data length: 7 bits
Stop bit
: 2 bits
Parity
: Even bits
0000 (fixed)
0000 to 0031
0000 (fixed)
*1*2

Advertisement

Table of Contents
loading

Table of Contents