Advanced commissioning
6.4 Setpoint calculation
6.4.4
Skip frequency bands and minimum speed
Skip frequency bands
The inverter has four skip frequency bands that prevent continuous motor operation within a
specific speed range. Further information is provided in function diagram 3050 of the List
Manual.
Minimum speed
The inverter prevents continuous motor operation at speeds < minimum speed.
Speeds where the absolute value is less than the minimum speed are only possible during
motor operation when accelerating or braking.
Table 6- 25
Parameter
p1080
p1106
174
Manuals for your converter (Page 335)
Setting the minimum speed
Description
Minimum rotation speed
Inverter factory setting (Page 98)
CI: Minimum speed signal source (factory setting: 0)
Dynamic specification of the minimum speed
Distributed converter for SIMOGEAR geared motors