Configuring the fieldbus
8.3 PROFIdrive profile for PROFIBUS and PROFINET
Overview of the response identifiers converter → control
The response identifier depends on the request identifier.
Table 8- 11
Response
identifier
0
1
2
3
4
5
6
7
8
1) The required element of the parameter is specified in IND (2nd word).
2) The required element of the indexed parameter is specified in IND (2nd word).
Overview of the error numbers in response identifier 7 (request cannot be processed)
For response identifier 7, the converter sends one of the following error numbers in the
highest word of the parameter channel to the control.
Table 8- 12
No.
00 hex
01 hex
02 hex
03 hex
04 hex
05 hex
06 hex
07 hex
0B hex
0C hex
11 hex
14 hex
100
Response identifiers converter → control
Description
No response
Transfer parameter value (word)
Transfer parameter value (double word)
Transfer descriptive element
Transfer parameter value (field, word)
Transfer parameter value (field, double word)
Transfer number of field elements
Request cannot be processed, task cannot be executed (with error number)
No master controller status / no authorization to change parameters of the parameter
channel interface
Error numbers for the response "Request cannot be processed"
Description
Illegal parameter number (access to a parameter that does not exist)
Parameter value cannot be changed (change request for a parameter value that cannot be
changed)
Lower or upper value limit exceeded (change request with a value outside the value limits)
Incorrect subindex (access to a subindex that does not exist. Additional diagnosis in error
value 2)
No array (access with a subindex to non-indexed parameters)
Incorrect data type (change request with a value that does not match the data type of the
parameter)
Setting not permitted, only resetting (change request with a value not equal to 0 without
permission)
Descriptive element cannot be changed (change request to a descriptive element that
cannot be changed. Additional diagnosis in error value 2)
No master control (change request but with no master control, see also p0927.)
Keyword missing
Request cannot be executed due to the operating state (access is not possible for
temporary reasons that are not specified)
Inadmissible value (change request with a value that is within the limits but which is illegal
for other permanent reasons, i.e. a parameter with defined individual values)
1)
2)
2)
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB