Installation
4.2 Electrical Installation
4.2.4

Grounding converter and motor

Grounding the converter
● Ground the converter via the PE connection in the mains supply connector.
● Ground the connectors as shown in the diagram below.
Image 4-5
• Connect the PE terminal on the left-hand
side of the converter to the metal frame it is
mounted on.
• Recommended cable cross section: 10 mm²
• Use a short wire connection preferably.
• Clean the connection to the steel
construction from paint or dirt.
• Use a ring clamp to ensure a good physical
connection which is resistant to accidental
disconnection.
Grounding the motor
● Ground the motor via the PE connection in the motor connector.
● Ground the connector as shown in the diagram above (grounding the converter).
Although the line and motor connectors are of a different type, the principle of grounding
them is the same.
● If possible, ground the motor housing.
38
Grounding the line supply and motor connectors
Operating Instructions, 07/2016, FW V4.7 SP6, A5E34262100B AD