M800/M80/E80/C80 Series Alarm/Parameter Manual
16 Machine Parameters
MDS-EM/EMH Series: Power supply type
Set as follows for the spindle drive section of the MDS-EM/EMH-SPV3.
bit F-C : amp
Not used. Set to "0".
bit B-8 : rtyp
Not used. Set to "0".
bit 7-0 : ptyp External emergency stop setting
Normal
MDS-EM:20, MDS-EMH:22
External emergency stop function
MDS-EM:60, MDS-EMH:62
MDS-EJ-SP Series: Regenerative resistor type
Set the regenerative resistor type.
bit F-8 : amp(bit F-C) / rtyp(bit B-8)
Setting prohibited
MR-RB12 or GZG200W39OHMK
MR-RB32 or GZG200W120OHMK 3 units connected in parallel : 14
MR-RB30 or GZG200W39OHMK 3 units connected in parallel : 15
MR-RB50 or GZG300W39OHMK 3 units connected in parallel : 16
Setting prohibited
Setting prohibited
FCUA-RB22
FCUA-RB37
FCUA-RB55
FCUA-RB75/2 1 unit
R-UNIT1
R-UNIT2
R-UNIT3
R-UNIT4
R-UNIT5
FCUA-RB75/2 2 units connected in parallel
FCUA-RB55/2 2 units connected in parallel
Setting prohibited
bit 7-4 : emgx External emergency stop function
Set the external emergency stop function.
0: Disable 4: Enable
bit 3-0 :
Not used. Set to "0".
ptyp
rtyp
amp
0
0
0 0
emgx
rtyp
amp
: 10-12
: 13
: 17-1F
: 20-23
: 24
: 25
: 26
: 27
: 28
: 29
: 2A
: 2B
: 2C
: 2D
: 2E
: 2F
593
IB-1501279-H