M800/M80/E80/C80 Series Alarm/Parameter Manual
15 User Parameters
#9606

HAND SHAKE

[M8]
Select the transmission control method.
"3" (DC code method) should be set for computer link B.
0: No control
1: RTS/CTS method
2: No handshaking
3: DC code method
#9607

TIME-OUT SET

[M8]
Set the time-out time at which an interruption of data transfer during data input/output should be detected.
"0" means infinite time-out.
---Setting range---
0 to 999 (1/10s)
#9608

DATA CODE

[M8]
Set the code to be used for the data description.
Refer to "#9603 PARITY EFFECTIVE".
0: ASCII code
1: ISO code
#9609
LINK PARAM. 1
[M8]
bit1: DC1 output after NAK or SYN
Select whether to output the DC1 code after the NAK or SYN code is output.
0: Not output the DC1 code.
1: Output the DC1 code.
bit7: Enable/disable resetting
Select whether to enable the resetting in the computer link.
0: Enable
1: Disable
#9610
LINK PARAM. 2
[M8]
Bit 2: Specify the control code parity (even parity for the control code).
Select whether to add an even parity to the control code, in accordance with the I/O device specifications.
0: Not add a parity bit to the control code
1: Add a parity bit to the control code
Bit 3: Parity V
Select whether to enable checking of parity V in one block at the input of the data.
0: Disable
1: Enable
#9611
Link PARAM. 3
[M8]
Not used. Set to "0".
#9612
Link PARAM. 4
[M8]
Not used. Set to "0".